Sales Helpline: +91-11-41860000 | Email: sales@stanlay.com

SFX16 2000J Cable Test & Fault Location System

SFX16 4/8/16KV Cable Fault locating system is a mobile system for testing and fault locating on low and medium voltage cables. Provided with ARM® (Arc Reflection Method) is used to pre-locate high resistance faults with its voltage levels of 4 – 8 – 16 kV the system is perfectly suited for the fault location in low voltage applications with available surge energy of 2000 Joule .SFX 16 includes the Teleflex SX control unit cum TDR.

Specifications
Product Specification

Range

20 m ...160 km @ v/2 = 80 m/μs

 

Pulse width

20 ns  ...10 μs

Pulse amplitude

10 ... 50 V

 

Accuracy of the 

distance measurement

 

±   0,2 % of the measuring range

 

Resolution

0.1 m @ v/2 80 m/μs, 1.0 cm @ v/2 < 40 m/μs

 

Sample rate

Up to 400 MHz

 

Gain

 

- 37 + 37 db

De-attenuation

0 ... + 22 dB for ProRange (adjustable 0 ... 100 %)

Propagation velocity v/2

10 ... 149,9 m/µs, ft/µs or nvp

Dynamic range

> 80 dB

Output impedance

50 Ω

Compensation

10 Ω ... 500 Ω, adjustable

 

ARM trigger

Automatic adaptation by ΔU Trigger or LÎH edge trigger

ARMslide

15 measurements in one ARM shot

Dead zone

None

Voltage proof input

< 400 V, operation only with separation filter

Display

10.4” color TFT XGA 1024x768, touchscreen, 600 cd/m2, LED-Backlight, dimmable

Data storage

2GB mSATA for program and data

Connectors

Ethernet, USB, BNC, CAN (LON optional)

Protection class

IP   65 closed, IP54 open lid

 

Supply

110 ... 240 V, 50/60 Hz, 30 VA 10 V ... 17 V DC, 3.8 A

Dimensions (W x H x D)

362 x 195 x 306 mm (option 19“, 6 HU)

Weight

10 kg

Operation temperature

- 10 °C + 50 °C

Storage temperature

- 20 °C + 60 °C

HV Module

Testing Surge

0 ... 24 kV

0 ... 4 kV; 2000 J

0 ... 8 kV; 2000 J

0 ... 16 kV; 2000 J

Burning

0 ... 16 kV; 200 mA

 

Surge rate

 

3 ... 10 sec, single pulse

Sheath fault locating

 

0 ...5 kV, 120 mA

Operation temperature

 

-10 °C ... + 50 °C

Weight

 

approx.  135 kg

Connection cables and supply

 

Connection cable

 

6m HV test leads

Mains supply

 

230 V; 50 Hz/2 kVA Isolation transformer 2 kVA (ca. 26 kg) (opt. 110 V step-up transformer)

Dimensions (W x H x D)

 

800 x 1280 x 800 mm

Features
Features
  • Safe and fast fault location with latest Teleflex SX technology
  • High surge energy for effective pinpoint locating
  • Various fault location methods include
 
 
Product Info Downloads
Product Info Downloads

Product Information files contain the essential technical detail you need to make informed decisions on any particular product. Simply click on a title to download a PDF copy of that file. If you wish a hard copy of a brochure, technical advice on any product or a demonstration then please contact us. We're always happy to help!

Title
File Type
File Size
Last Uploaded
application/pdf
1.09 MB
August 12 2019 15:09:49
 
 

Related Products

Get In Touch
Want to Know More About our Products ?

Contact us today to find out more. We have our sales representative ready to help you with any subject matter related to our products

Top Categories