PS4500 Power Quality Analyzer
The PS4500 Power Quality Analyzer is the best choice if you are looking for a versatile, easy-to-use power quality analyzer that can record energy use, log voltage and current, plus capture power quality events such as transients, sags, swells and track harmonic distortion. Use it on single phase or three phase circuits and loads. You can also add the AMD option for performing on-line electric motor diagnostics using Motor Current Signature Analysis (MCSA).
The industry’s highest safety standard. CAT IV
The industry’s highest sampling rate for RMS. V, A, W, etc calculated
   based on 2,083 samples per cycle.
• Swell, sag, and inrush detection of every half cycle of all three voltages
  and all four currents, simultaneously, while doing all other functions
Complete Harmonic Analysis simultaneously on every cycle of every input,
   while doing all other functions.
• True High-Speed Transient detection and waveform capture    simultaneously on  all inputs, while doing all other functions.
Complete power/energy/cost analysis of any AC or DC power system, while   measuring harmonic, swell, sag, and true high-speed transient analysis on all inputs.
 Compatible with VSD outputs. 22-200 Hz, 360-440 Hz and DC power
Wireless Communications with Bluetooth technology.
“Foolproof” Connections with SureStartTM patent-pending technology.
Provision for Removable Memory with slot for SD memory.
Advanced Options such as on-line motor analysis utilizing CSA (AMD option)   and   power-line noise spectrum analysis (FAO option).
Complete logging, custom triggering, and waveform capture capability.



Provided with power analysis software tool that performs complete presentation and analysis of power consumption and Report Writer software which provides concise summaries including comparisons of performance.




Measurement Rate:
Samples every cycle of every input, voltage and current at 2083 samples per cycle (8 µseconds). All measurements updated once per second
Voltage Measurement Ranges:
1-600 Vrms steady-state(direct input);
or 600–5,000 Vrms with 5 KVP probes,
or 600–15,000 Vrms with 15 KVP probes.
Display Range: 1-6 MV (using input ratios)
Accuracy: 0.1% of reading ±0.3 Vrms
Current Measurement Ranges:
With HA5: 0.02-5A
With HA100: 0.1-100A
With HA1000: 1-1000A
With FX3000: 10-3000A
With FX5000: 100-5000A
With DC600: 5-600 A DC
Diplay Range: 1 mA-6MA(using input ratios)
Accuracy:0.1% of reading plus accuracy of probe
Frequency Measurement:
Range: DC, 22-200Hz, 360-440 Hz fundamental
Accuracy:±0.25%
Harmonics Measurement:
22-3900Hz(65th harmonic @ 50/60 Hz)
Accuracy:0.25%
THD Accuracy:
THD and individual harmonics through 25th(1800 Hz) of all signals. With PowerSight Manager PC Software displays harmonics through 65th harmonic
Power, Energy, Cost, Power Factor:
Display Range: 1 watt-60MW (using input ratios)
Accuracy: 0.5% plus accuracy of current probe
Swell/Sag Detection
Response: 1/2 cycle
Transient Detection: High Speed Transient Sampling every 8 µsec
Waveform Snapshot: User captured waveforms set by user allocation of memory
Logging Period (resolution): User selectable from 1 second — 99 minutes
Logging Duration(length of monitoring session) User selectable up to 2 years according to memory allocation
Power Requirement: 12 VDC@500mA, wall-mount power supply included. Internal Ni-Cad battery operates 8-10 hours after full charge
Size:196x40x54mm
Weight:0.5kg