While there are many ways available for water leak detection of buried water pipes, Acoustic leak detection method remains the first choice for detecting and locating pipeline leaks. In Acoustic Leak Detection Method, the underground water leak detector identifies the leakage sound with the help of listening equipment & pinpoint the exact locations of water leaks in buried water pipes laid in cities, towns, industrial & residential areas.
The leakage sound consists of four sounds: water flow sound, impact sound, friction sound & vibration sound. The closer an operator gets to the leak point, the intensity/strength of the signal will increase. The underground leak detection system detects the leakage sound & by figuring out the highest sound intensity & pinpoints the exact damaged location.
Stanlay offers latest generation PERIJA PLUS smart acoustic water pipe leak detection equipment, based on a piezo electric ground microphone coupled with an advanced controller for identifying leaks in all types of pressurized buried water pipe networks, metallic and non-metallic water pipe networks, in both the main lines and branches of metro, industrial and irrigation environment for pipe sizes upto 750mm.
Product
|
Perija Plus
|
Perija Mini V-Pickup
|
Perija Mini VPro
|
Application
|
Water leak detector for buried water pipes in City/Town Mains & Branch lines & Fire Hydrant pipes
|
Water leak detection in residential & Campus, Service lines, Pipes In Building floors, Floors & Below ground
|
Electronic listening stick
+ water leak judgement between service lines between one home/ building to another
|
Placement of sensor
|
On ground surface for water leak detection of buried water pipes
|
On ground, floor or walls
|
On Pipe/valve near water meter
|
Frequency range
|
100 to 1200Hz
|
200 to 4000Hz
|
200 to 4000Hz
|
Band Pass Filters
|
9
|
4
|
4
|
Amplification
|
59dB +/-3
|
53dB +/-3
|
53dB +/-3
|
Controller
|
Display controller with 5” display
|
N/A – Display on User mobile phone App
|
N/A – Display on User mobile phone App
|
Minimum Water Pressure
|
>=2 Bar
|
>=1.5 Bar
|
N/A
|
Max Depth of Pipe
|
5 meters
|
1.8meters
|
N/A
|
Max Pipe Size
|
750mm
|
Typically upto 600mm
|
N/A
|
Pipe Type
|
Metallic & Non Metallic including PVC
|
Metallic & Non Metallic including PVC
|
Metallic & Non Metallic including PVC
|
Automatic Leak Judgement Mode
|
N/A
|
Yes
|
Yes
|
FiltROT mode for best filters
|
Yes
|
Yes
|
Yes
|
Notch Filter for removal of 50/60Hz Power grid noise from audio
|
N/A
|
Yes
|
Yes
|
Piezoelectric sensor
|
External (equipped with characteristic ball to break wind & filter noise) IP-67 equivalent (water depth 1m, 30 minutes)
|
External (equipped with characteristic ball to break wind & filter noise) IP-67 equivalent (water depth 1m, 30 minutes)
|
Internal (electronic listening stick)
|